VU-8213-686-5-14
Globe Valve Assembly, 2 Way, 4 in.
            by
        
        done_outline8888 in stock
        
            addShow Locations
            removeHide Locations
        
    Flanged Connection, 145 Cv, Cast Iron Body, Brass Trim, Direct Coupled Actuator, 337 ft.-lb., Non-Spring Return, 24 VAC/DC, Floating Or Proportional Control Signal, 0 To 10 VDC, 2 To 10 VDC Or 4 To 20mA Control Signal, 2 To 10 VDC Feedback.
Features
                    Balanced Plug Technology
                
                            
                    Easy One Touch Input Signal/Stroke Calibration
                
                            
                    Excellent Close-Off Capability Up To 125 psi
                
                            
                    Meets ANSI IV Seat Leakage Specifications
                
                            
                    Self-Adjusting Spring-Loaded TFE/EPDM Packing
                
                            
                    U-Bolt Style
                
                            
                    Floating Configuration Controlled By A SPDT Floating Controllers
                
                            
                    Direct/Reverse Action Switch Selectable
                
                            
                    Manual Override To Allow Positioning Of Valve
                
                            
                    Torque Overload Protection Throughout Stroke
                
                        Technical Details
                            Service
                        
                        
                            Glycol 25 To 50%, Steam, Water
                        
                    
                            Flow Characteristic
                        
                        
                            Modified Equal Percentage
                        
                    
                            Operating Conditions
                        
                        
                            20 F To 281 F (-7 C To 138 C)
                        
                    
                            Stem Action
                        
                        
                            Up Open
                        
                    
                            Power Consumption
                        
                        
                            24 VAC
                        
                    
                            Operating Conditions
                        
                        
                            -13 F To 149 F (-25 C To 65 C)
                        
                    
                            Housing
                        
                        
                            NEMA 1 Or NEMA 2, IP54