NPT, 11.7 Cv, Forged Brass Body, Stainless Steel Ball And Blowout-Proof Stem, Direct Mount Electric Actuator, 27 lb-in. Spring Return, 24 VAC, 0 To 10 VDC, Proportional.
Features
Blow-Out Proof Stem Protects The User From The Risk Of Injury
Technical Details
Service
Hot Water, Chilled Water, 50/50 Glycol Solution For HVAC Systems
Flow Characteristic
Equal Percentage On The In-Line Port A (Coil) And Linear Of The Angle Port B (Bypass)
Operating Conditions
23 F To 203 F (-5 C To 95 C)
Close-Off Pressure
200 psig
Power Consumption
5.1 VA Running, 2.8 VA Holding
Operating Conditions
-22 F To 140 F (-30 C To 60 C)
Electrical Connection
48 in. 18 AWG Appliance Cables With Integral 3/8 in. FMC Connectors