    Programmer, Valve proof of closure, selectable purge, PTFI timing, intermittent or interrupted, recycle / non-recycle operation, reset by power interruption of manual reset.
Features
                    Operating Temperature: -40 F (-40 C) To 140 F (60 C)
                
                            
                    Terminal 6 Operating Limit Input
                
                            
                    15 Second Post Purge Time After Operating Limit Open With Flame Present
                
                            
                    10 Second Post purge Time After Flame Fail During PTFI, STABILIZATION, And MTFI Period
                
                            
                    Reset From Lockout Achievable From Local Reset Push Button Or Line Power
                
                            
                    LED Will Be Illuminated As Long As Power Applied To Terminal 1
                
                            
                    MEC320 Type Chassis Required
                
                            
                    Purge Time: User Selectable 0, 5, 15, 30, 60, 90, 120, 240 Seconds
                
                            
                    Pilot Trial For ignition Period (PTFI): User Selectable 5 (Closed) Or 10 Seconds (Open) Fixed
                
                            
                    Pilot Solenoid Operation, Terminal 3 User Selectable Interrupted Or Intermitten
                
                            
                    5 Second Main Trial For Ignition Period
                
                            
                    Lockout Action On Pilot Flame Fail
                
                            
                    Lockout On Pilot Proving Period Flame Fail
                
                            
                    Lockout Action On Main Trial For Ignition Period Flame Fail