    Programmer, provides selectable PTFI, selectable baud rate, and selectable recycle / non-recycle operation. For use with MEC320TS chassis only.
Features
                    Fixed 30 Second Pre-Purge Period
                
                            
                    Ignition Terminal 4 Shuts Off 10 Seconds Into The Pilot Trial For Ignition
                
                            
                    5 Second Pilot Proving Period
                
                            
                    Pilot Terminal 3 Shuts Off 5 Seconds Into The Main Trial For Ignition
                
                            
                    Post Purge Has Selectable 0 Or 60 Seconds Duration
                
                            
                    Release To Modulate Contacts Change State 1 Second Into AUTO (MEC320TS Required)
                
                            
                    Lockout Occurs If Air Flow, Terminal 6, Is Not Proven 10 Seconds Into Purge
                
                            
                    Dip Switch Selectable Communication Baud Rate, 4800, 9600 Or 19200 Baud
                
                            