RM7888A1027/U
PLC Adaptable Primary Control
by
done_outline8888 in stock
addShow Locations removeHide Locations
120 VAC, 50/60 Hz., Selectable Pilot Type, 15 Second Main Flame Establishing Period, 10 Second Pilot Flame Establishing Period, For 10 Second DSI Applications, Selectable Sequences.

Features

Functions Include Automatic Burner Startup Sequencing, Five User Selectable Run Sequences, Four Line-Voltage Sequence Control Inputs, Flame Supervision, System Status Indication, System Or Self Diagnostics And Troubleshooting
Requires A Relay Module, Subbase, And Amplifier For Operation
Options Include PC Interface, Keyboard Display Module, DATA CONTROLBUS MODULE, Remote Display Mounting, First-Out Expanded Annunciator, And COMBUSTION SYSTEM MANAGER Software
Use With Master System Control Which Determines Purge Timing And Confirms Air Supply And Air Flow
Non-Volatile Memory Retains History Files And Lockout Status After Loss Of Power
Five LEDs Provide Sequence Information
Interchangeable Plug-In Amplifiers
Local Or Remote Annunciation Of Operation And Fault Information
Optional Remote Reset Capability

Technical Details

Application
Primary Control- PLC Adaptable
Operating Conditions
-40 F To 140 F